Inspections
The most recent comprehensive inspection of Parkview Nursing and Rehabilitation Center occurred on July 31, 2024, 22 violations of state standards were cited.
Findings
(May include findings from previous inspections)
Health Code
| Date | Corrected | State Violation Cited |
|---|---|---|
| 7/31/2024 | 8/1/2024 | The facility did not store, cook, and give out food in a safe and clean way. |
Life Safety Code
| Date | Corrected | State Violation Cited |
|---|---|---|
| 11/8/2023 | 11/20/2023 | The facility failed to maintain smoke barriers so smoke cannot spread during a fire. |
| 11/8/2023 | 12/23/2023 | The facility failed to make sure the finishes on walls, ceilings and floors could be easily cleaned and sanitized. |
| 11/8/2023 | 12/23/2023 | The facility failed to provide enough light in rooms based on how the room is used. |
| 11/8/2023 | 12/15/2023 | The facility failed to keep documentation of compliance with this subsection at the facility. |
| 11/8/2023 | 11/15/2023 | The facility failed to document compliance. |
| 11/8/2023 | 12/15/2023 | The facility failed to have a program to maintain, operate and test all emergency generators and to execute the program every week. |
| 11/8/2023 | 12/15/2023 | The facility failed to make sure the person who executes the emergency generator maintenance, operation and testing program is properly instructed in the tasks. |
| 11/8/2023 | 12/15/2023 | The facility failed to make sure generator components are inspected, tested and maintain according to NFPA standards. |
| 11/8/2023 | 12/15/2023 | The facility failed to make sure generators are operated under load at least 30 minutes each week. |
| 11/8/2023 | 12/15/2023 | The facility failed to failed to make sure the person executing the generator program signed and dated records of inspections, tests and maintenance performed. |
| 11/8/2023 | 12/15/2023 | The facility failed to make sure each required operation of the generator was documented, including information necessary to verify the total time it took for the generator to pick up the load, the total time the generator operated under load, the total time the generator continued to operate under load after the normal utility power was restored, and the total time the generator operated after the load was transferred back to the normal utility power. |
| 11/8/2023 | 12/15/2023 | The facility failed to make sure documentation of compliance was kept onsite. |
| 11/8/2023 | 12/1/2023 | The facility failed to have the gas piping lines tested annually by a person licensed by the State Board of Pluming Examiners; failed to maintain a written signed report of these tests, or failed to immediately correct unsatisfactory conditions. |
| 11/8/2023 | 12/23/2023 | The facility failed to make sure walls and ceilings are easily cleaned and are kept looking nice and neat. |
| 11/8/2023 | 12/23/2023 | The facility failed to ensure the fire marshal inspects the facility annually. |
| 11/8/2023 | 12/23/2023 | The facility failed to include a risk assessment, a description of the resident population including services and assistance they require, a section for each core function of emergency management, a fire safety plan in their emergency preparedness and response plan, or a section for self reporting incidents. |
| 11/8/2023 | 12/23/2023 | The facility failed to train staff on their responsibilities under the emergency preparedness and response plan. |
| 11/8/2023 | 12/23/2023 | The facility failed to make sure the fire alarm system was installed by qualified people. |
| 11/8/2023 | 11/13/2023 | The facility failed to make sure smoke barriers are constructed correctly to prevent the spread of smoke. |
| 11/8/2023 | 11/10/2023 | The facility failed to make sure the kitchen exhaust system was installed correctly. |
| 11/8/2023 | 12/23/2023 | The facility failed to make sure finishes on the surfaces of walls, ceilings and floors are easily cleanable. |
Enforcement Actions
No enforcement actions found.