The most recent comprehensive inspection of AUTUMN LEAVES occurred on June 13, 2024, 12 violations of state standards were cited.
Findings
(May include findings from previous inspections)
Health Code
| Date | Corrected | State Violation Cited |
|---|---|---|
| 6/12/2024 | 6/13/2024 | The facility did not store, cook, and give out food in a safe and clean way. |
Life Safety Code
| Date | Corrected | State Violation Cited |
|---|---|---|
| 6/13/2024 | 7/1/2024 | The facility failed to the meet Life Safety Code requirements for an existing Health Care Occupancy. |
| 6/13/2024 | 7/22/2024 | The facility failed to provide emergency power for lighting in the specified areas when the power goes off. |
| 6/13/2024 | 7/19/2024 | The facility failed to make sure the fire alarm and fire sprinkler systems are installed and working correctly. |
| 6/13/2024 | 7/19/2024 | The facility failed to make sure air conditioners shutoff to prevent the spread of smoke when the fire alarm goes off. |
| 6/13/2024 | 6/17/2024 | The facility failed to make sure the fire alarm is activated if the fire sprinklers go off and that conditions that cut off the water for the fire sprinklers are reported. |
| 6/13/2024 | 7/9/2024 | The facility failed to maintain smoke barriers so smoke cannot spread during a fire. |
| 6/13/2024 | 7/22/2024 | The facility failed to provide enough light in rooms based on how the room is used. |
| 6/13/2024 | 7/5/2024 | The facility failed to maintain the fire alarm system components in compliance with the requirements of the NFPA code. |
| 6/13/2024 | 7/15/2024 | The facility failed to make sure generator components are inspected, tested and maintain according to NFPA standards. |
| 6/13/2024 | 7/22/2024 | The facility failed to conduct a functional test on every required battery emergency lighting system at 30-day intervals for a minimum of 30 seconds; failed to conduct an annual test for a minimum of 1 1/2 hours; or failed to document the tests that were performed and have those records available to the authority having jurisdiction. |
| 6/13/2024 | 8/9/2024 | The facility failed to make sure walls and ceilings are easily cleaned and are kept looking nice and neat. |