Inspections
The most recent comprehensive inspection of Orchard Park at Southfork occurred on December 15, 2021, 13 violations of state standards were cited.
Findings
(May include findings from previous inspections)
Health Code
| Date | Corrected | State Violation Cited |
|---|---|---|
| 12/15/2021 | Pending |
Life Safety Code
| Date | Corrected | State Violation Cited |
|---|---|---|
| 2/11/2020 | 2/12/2020 | The facility failed to ensure that locking devices on exit doors released when the fire alarm or sprinkler system were activated. |
| 2/11/2020 | 2/12/2020 | The facility failed to ensure that locking devices on exit doors released when a switch or button was activated at the monitoring station and at the main staff station. |
| 2/11/2020 | 2/24/2020 | The facility failed to provide a manual fire alarm pull within five feet of each exit door with a sign stating, "Pull to release door in emergency." |
| 2/11/2020 | 2/24/2020 | The facility failed to comply with Chapter 19 of NFPA 101. |
| 2/11/2020 | 2/24/2020 | The facility failed to provide lighting levels in compliance with licensing standards for assisted living facilities. |
| 2/11/2020 | 2/24/2020 | The facility failed to provide a written contract with a fire alarm firm to perform inspections, testing, and system maintenance at least every six months. |
| 2/11/2020 | 2/24/2020 | The facility failed to ensure the smoke detectors were to be tested for sensitivity as required. The facility failed to provide all required fire alarm documentation, including as-built installation drawings, operation and maintenance manuals, and a written sequence of operation, must be available for examination by DADS. |
| 2/11/2020 | 2/24/2020 | The facility failed to ensure the required sprinkler system was inspected, tested, and maintained in compliance with NFPA 25. |
| 2/11/2020 | 3/24/2020 | The facility failed to provide operable windows or powered exhaust that is required for all odor-producing rooms. |
| 2/11/2020 | 2/24/2020 | The facility failed to ensure the building was kept in good repair. |
| 2/11/2020 | 2/24/2020 | The facility failed to provide an initial gas pressure test of the gas lines from the meter; and/or failed to ensure additional gas pressure tests were performed when gas service was interrupted; and/or that all gas heating systems were documented |
| 2/11/2020 | 2/12/2020 | The facility failed to provide and/or maintain a commercial range hood and exhaust system in compliance with NFPA 96. |
Enforcement Actions
Date of Action
9/8/2025
Action Taken
Administrative Penalty
Final Assessed Amount
$3750.00
Related Violations
| TAC | State Violation Cited |
|---|---|
| 553.104(c) | The facility failed to have a complete fire safety plan for the protection of everyone in the facility in the event of a fire. |