Inspections
The most recent comprehensive inspection of SHEPHERD PERSONAL CARE HOME INC. occurred on June 20, 2023, 8 violations of state standards were cited.
Findings
(May include findings from previous inspections)
Health Code
| Date | Corrected | State Violation Cited |
|---|---|---|
| No Health Code violations found | ||
Life Safety Code
| Date | Corrected | State Violation Cited |
|---|---|---|
| 11/23/2020 | 11/24/2020 | The facility's emergency preparedness and response plan failed to address the eight core functions of emergency management. |
| 11/23/2020 | 11/24/2020 | The facility failed to ensure the primary power source for the fire alarm system was on a dedicated electrical circuit. |
| 11/23/2020 | 11/24/2020 | The facility failed to provide a written contract with a fire alarm firm to perform inspections, testing, and system maintenance at least every six months. |
| 11/23/2020 | 11/24/2020 | The facility failed to ensure the smoke detectors were to be tested for sensitivity as required. The facility failed to provide all required fire alarm documentation, including as-built installation drawings, operation and maintenance manuals, and a written sequence of operation, must be available for examination by DADS. |
| 11/23/2020 | 11/24/2020 | The facility failed to ensure the required sprinkler system was inspected, tested, and maintained in compliance with NFPA 25. |
| 11/23/2020 | 11/30/2020 | The facility failed to ensure the outside areas, grounds, adjacent buildings, and all site features were maintained free of fire or health hazards; and/or failed to ensure that water would drain away from the facility to prevent standing water near the building. |
| 11/23/2020 | 11/24/2020 | The facility failed to implement procedures that assure safe and sanitary use and storage of oxygen. |
| 11/23/2020 | 11/24/2020 | The facility failed to ensure hot water for resident use was maintained between 100 degrees Fahrenheit and 120 degrees Fahrenheit. |
Enforcement Actions
No enforcement actions found.